Series 919
Reduced Pressure Zone
Assemblies
Sizes:
1
⁄4" – 2" (5 – 50mm)
Series 919 Reduced Pressure Zone Backflow Assemblies are
designed to protect potable water supplies in accordance with
national plumbing codes and water authority requirements. This
series can be used in a variety of installations, including the preven-
tion of health hazard cross-connections or for containment at the
service line entrance.
This series features two poppet style check valves, replaceable
check seats, with an intermediate relief valve. Its compact modular
design facilitates easy maintenance and assembly access. Sizes
1
⁄4"
– 1" (5 – 25mm) shutoffs have tee handles.
Features
•Separateaccesscoversforthecheckvalvesandreliefvalvefor
ease of maintenance
•Topentry-allcheckinternalseasilyaccessible
•Allrubberelastomersofchloramineresistantmaterial
•Checkvalvepoppetassembliesarefullyguidedbyinnovative
plastic seat guide
•Replaceablepush-incheckvalveandreliefvalveseats
eliminates threads from the water way
•EZtwistreliefvalvecoverquarter-turnlockingjointcaptures
the spring load during repair to facilitate disassembly
•Innovativecheckvalveplasticcoverbushingprovidestrouble
free guiding of the check valve poppet
•Bottommountedreliefvalveprovidesreducedinstallationclear-
ances
•Compact,spacesavingdesign
•Nospecialtoolsrequiredforservicing
•Topmountedtestcocksforeaseintestingandreducedinstalla-
tion clearances
•StandardlyfurnishedwithNPTbodyconnections
Specifications
A Reduced Pressure Zone Assembly shall be installed at each
potential health hazard location to prevent backflow due to back-
siphonage and/or backpressure. The assembly shall consist of a
pressure differential relief valve located in a zone between two posi-
tive seating check valves. Seats and seat discs shall be replace-
able in both check valves and the relief valve without the use of
special tools. Service of all internal check valve components shall
be through top mounted access bronze covers threaded to the
main valve body. The check valve poppet assembly shall be guided
via the use of a corrosion resistant plastic guide. The check valve
and relief valve seats shall be push-in type. The relief valve cover
shall be bronze construction secured with stainless steel bolts and
shallutilizeaquarter-turnlockingjointtocapturethespringload
of the relief valve. The relief valve shall have an internal sensing line
to sense the inlet water supply. All rubber elastomers shall be of
chloramine resistant material. The assembly shall also include two
resilient seated isolation valves, four top-mounted resilient seated
test cocks and an air gap drain fitting. The assembly shall be a
Watts Series 919.
For Health Hazard Applications
919QT
3
⁄4" (20mm)
Now Available
WattsBox Insulated Enclosures.
For more information, refer to literature ES-WB.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
JobName
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’sP.O.No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
ES-919