RP/IS-994/994RPDANOTICEInquire with governing authorities for local installation requirements NOTICEFor Australia and New Zealand: Pipeline strainers
2Location and Installation Considerations1. Backflow preventers must be installed in high-visibility lo ca tions in order to allow for immediate noti
3Series 994 Installation Instructions*For additional information on Watts insulated enclosures refer to literature ES-WB.ParallelIndoorsAbove Ground12
4Servicing First and Second ChecksSeries 994/994RPDA 4" and 6" (100 – 150mm)Removing Check Assemblies (Before servicing be sure shutoff valv
5Servicing First and Second ChecksSeries 994/994RPDA 8" and 10" (200 – 250mm)1. Slowly open all ball valves to relieve air and water press
6Servicing the Relief Valve 1. The relief valve may be serviced while on or off the backflow preventer valve. 2. NOTICE DO NOT USE A PIPE WRENCH
7Testing - Reduced Pressure Zone AssembliesWatts TK-DLThe following Test Procedure is one of several that is recognized throughout the United States f
Problem Cause SolutionA. Assembly discharges from differential relief valve during no flow condition.Fouled first check Disassemble and clean No. 1 c